PHYM series pressure foam liquid storage tank

NegotiableUpdate on 10/04
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

PHYM series pressure type foam liquid storage tank I. Description: foam liquid is stored in a rubber made thin-wall rubber capsule with high strength, high elasticity and high flexibility. Pressure water only enters and exits the capsule, separated from foam liquid. The remaining foam liquid after fire fighting can still be used, saving foam liquid and reducing fire fighting cost

Product Details

PHYM series pressure foam liquid storage tank

1、 Explanation
High strength, high elasticity and high flexibility thin wall rubber capsules made of rubber are used to store foam liquid inside. Pressure water only flows in and out of the capsules and is separated from foam liquid. The remaining foam liquid can still be used after extinguishing the fire, saving foam liquid and reducing the cost of extinguishing the fire. With this tank fire extinguishing system, the mixing ratio is quite stable, accurate and reliable, and can provide high-quality foam mixture. With this type of tank, the pressure loss of mixing is the smallest, the foam ejected has large energy and strong penetration ability. High, medium and low expansion foam devices can be used.

work pressure 0.6~1.6 MPa
rated pressure 1.0 MPa
Test pressure intensity 2.4 MPa
seal 1.8 MPa
Tank capacity 500~100000 L
Equipped with a proportional mixer PHY4~100
Proportional mixer mixing ratio 3% or 6%

2、 Product structure and main technical parameters
PHYM系列压力式泡沫液储罐(图1)
Main technical parameters

Foam model Proportional mixer (PHY) provided water inlet
(DN)
Mixed liquid outlet
(DN)
drain outlet
(DN)
slag discharge port
(DN)
L L2 H
PMG5 PHY4 DN50 DN50 DN20 DN20 1465 1078 660
PMG10 PHY8 DN65 DN65 DN25 DN25 1790 1303 735
PHY16 DN100 DN100 DN32 DN32 1340
PMG15 PHY8 DN65 DN65 DN25 DN25 2460 1303 735
PHY16 DN100 DN100 DN32 DN32 1340
PMG20 PHY16 DN100 DN100 DN32 DN32 2370 1544 812
PHY24 DN150 DN150 DN50 DN50 1609
PMG25 PHY16 DN100 DN100 DN32 DN32 2830 1544 812
PHY24 DN150 DN150 DN50 DN50 1609
PMG30 PHY24 DN150 DN150 DN50 DN50 2900 1699 837
PHY32
PMG40 PHY24 DN150 DN150 DN50 DN50 2670 2183 915
PHY32
PMG50 PHY32 DN150 DN150 DN50 DN50 3190 2183 915
PHY48
PMG55 PHY32 DN150 DN150 DN50 DN50 3454 2183 915
PHY48
PMG76 PHY48 DN150 DN150 DN50 DN50 3197 2587 1045
PHY64 DN200 DN200 DN65 DN65 2630
PMG80 PHY48 DN150 DN150 DN50 DN50 3330 2587 1045
PHY64 DN200 DN200 DN65 DN65 2630
PMG100 PHY64 DN200 DN200 DN65 DN65 4000 2630 1045
PHY76
PMG110 PHY64 DN200 DN200 DN65 DN65 4333 2630 1045
PHY76
PMG130 PHY76 DN200 DN200 DN65 DN65 4285 2737 1125
PHY100 DN250 DN250 2769

3、 Instructions for use
1. When selecting, indicate the model of the proportional mixer used;
2. The size and piping connected to the proportional mixer are the responsibility of our company;
3. It needs to be ordered separately with the special pump assembly for foam concentrate injection as an accessory;
4. Installing a liquid level gauge as an accessory requires separate ordering;
5. The foam liquid storage tank above 4000L is equipped with a climbing ladder;
6. The foam liquid storage tank larger than 10000L should not be used.