Overview: YJ-G-L/H/T/S single flange differential pressure/pressure transmitter is used to measure media containing solids, precipitated liquids, and steam. Its membrane box is used to prevent the medium from directly entering the pressure sensor component of the differential pressure transmitter, causing inaccurate measurement of the transmitter or direct damage to the sensor. It uses filling liquid such as silicone oil to transmit pressure between it and the transmitter. Oil and other filling fluids transmit pressure. YJ-G-L/H/T/S single flange differential pressure/pressure transmitter is used to measure the liquid level of liquids, gases, or vapors. Density, pressure, and flow rate, then convert them into 4~20mADC HA
Product Details


Overview

YJ-G-L/H/T/S single flange differential pressure/pressure transmitter is used to measure the presence of

Solid and precipitating liquids, as well as steam and other media. Its membrane box is used to prevent media

Directly entering the pressure sensor component of the differential pressure transmitter, causing the transmitter to measure

Inaccurate measurement or direct damage to the sensor, using silicon between it and the transmitter

Oil and other filling fluids transmit pressure.

YJ-G-L/H/T/S single flange differential pressure/pressure transmitter for measuring liquids

The liquid level of a body, gas, or vapor. Density, pressure, and flow rate, and then

It is converted into a 4-20mADC HART current signal output. Can be used with HART hand

Operators communicate with each other Set up. Monitoring, etc.

Technical Specifications

Measurement parameter: differential pressure Liquid level pressure

Measurement range: Lower limit value: Starting from -100% URL (continuously adjustable)

Upper limit value: up to+100% UFL (continuously adjustable by 1)

range

Table 1 Comparison Table of Range Code and Range Range Relationship

Minimum range and maximum range of normal range

Rated pressure (maximum value)

code

B

1Pa

6kPa

4xPa '

40kPa

2KPa 250kPa

Rated pressure of flange

200kPa 700kPa

Table 2 Comparison Table of Flange and Minimum Range Relationship

Liquid level flange

Nominal diameter

minimum range

DN 50/2 surface

10kPa

flat

DNBO/3.

2kPa

DN41

2kPa

DN50/2 1

16kPa

plug-in

DN80/31

2kPa

DN4

2kPa

The minimum range of the differential pressure transmitter should be the minimum range in Table 1 and Table 2

The larger value. The range of adjustment shall not be less than the minimum range. Maximum quantity of transmitter

Cheng should be the minimum value between the maximum range of the transmitter body and the rated pressure of the flange.

lose

go out

Output signal

2-wire system. 4-20mADC HART output, digital communication. HART protocol

Load on 4-20mADC signal. Output signal limit: lmin=3.8rmA,

B Beauty

Imax- 20.5mA

Alarm current (mode can be set)

Low alarm mode (minimum): 3.6mA High alarm mode (maximum 1.21mA)

Do not report mode (maintain); Maintain the effective current value before the fault

Alarm current standard setting: high alarm mode