Sichuan customized 35KV high-voltage isolation switch

NegotiableUpdate on 12/11
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
Description: Sichuan customized 35KV high-voltage isolation switch is not suitable for places with flammable substances, explosion hazards, chemical corrosion, and severe vibration. Explanation: When the above environmental conditions cannot meet the usage requirements, it shall be resolved through negotiation between the user and the manufacturer. This series of products meets the requirements of standards and IEC standards, with good seismic resistance and the ability to meet the requirement of a seismic intensity of 9 degrees.
Product Details

Sichuan customized 35KV high-voltage isolation switch

This series of products includes the following varieties:
1) Divided by the presence or absence of a grounding switch: ungrounded, single grounded (left and right grounded), and double grounded;
2) Grounding switches are classified into types I, II, and III based on their ability to withstand short-circuit currents;
3) Divided by usage area: ordinary type, anti fouling type, anti fouling type, and high-altitude type.
This series of products meets the requirements of standards and IEC standards, with good seismic resistance and the ability to meet the requirement of a seismic intensity of 9 degrees.
Sichuan customized 35KV high-voltage isolation switch
Conditions of Use
1. The altitude shall not exceed 1000m, and the plateau type shall not exceed 4000m;
2. Environmental temperature: -40 ℃ to+40 ℃;
3. Wind speed not exceeding 35m/s;
4. Earthquake intensity: 8 degrees;
5. Ice thickness: ≤ 10mm;
6. Anti pollution products are suitable for polluted areas;
7. Not suitable for places with flammable substances, explosion hazards, chemical corrosion, and severe vibrations.
Explanation: When the above environmental conditions cannot meet the usage requirements, it shall be resolved through negotiation between the user and the manufacturer.

Technical Parameter

Rated voltage KV: 40.5

Rated frequency Hz: 50/60

3 Rated current A: 630/1250/2500

4 rated short-circuit breaking current KA: 20/25/31.5

5 rated short-circuit current breaking times: 30

6 rated peak withstand current KA: 63/80

7 rated short-circuit closing current (peak) KA: 63/80

8 mechanical life cycles: 10000

9 4S short-time withstand current KA: 25/31.5

10 power frequency withstand voltage (1 minute): dry test (phase to phase, ground/fracture) KV: 80 95/95

11 lightning impulse withstand voltage (peak) phase to phase, relative/fracture KV: 185

12 rated operating cycles: on-off -0.1s-on-off -3s on-off -6-son-off -60s on-off -60s restoration

13 institutions control voltage AC/DC220