Welcome Customer !

Membership

Help

Kuaida Fire Protection Technology Co., Ltd
Custom manufacturer

Main Products:

ybzhan>Products

Kuaida Fire Protection Technology Co., Ltd

  • E-mail

    zhjchfm609@163.com

  • Phone

    13484338206

  • Address

    Donggong Industrial Park, Ruanshi Town, Zhuji City, Zhejiang Province

Contact Now

Tank fire sprinkler cooling device

NegotiableUpdate on 10/04
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

With the continuous and rapid development of the petrochemical industry, the fire cooling and sprinkler system for steel (spherical, vertical) storage tanks

Product Details

Fire cooling sprinkler system for steel (spherical, vertical) storage tanks
With the continuous and rapid development of the petrochemical industry, our company conducted research and analysis on the current market. Based on the "Fire Prevention Code for Petrochemical Enterprise Design", "Design Code for Automatic Sprinkler Fire Extinguishing System", "Design Code for Petroleum Storage" and "Design Code for Crude Oil Storage", and leveraging our own technological advantages and years of production experience, after one year of research and development, we have developedFire cooling sprinkler system for steel storage tanksThe device has replaced the traditional method of drilling holes in pipelines for tank cooling, and has adopted multiple advanced processes and anti-corrosion techniques in production, resulting in a service life of over 20 years.
Fire cooling sprinkler system for steel storage tanksSuitable for protective cooling and fire isolation of flammable and explosive gas and liquid storage tanks in the petroleum and chemical industries, which can effectively control the spread of fire. Different cooling spray devices can also be designed according to different non-standard storage tanks of users. Since its commissioning, the device has been widely recommended by relevant design units and has been widely adopted by users and fire management departments.

Fire cooling sprinkler system for steel storage tanks
Design Specifications

1、 This device is suitable for the protective cooling of Class A, B, and C liquid and combustible gas storage devices in the petrochemical industry, as well as special equipment for petroleum and chemical industry - tower equipment.

2、 Design and material selection reference standards:

GB50160-92 (1999 edition)
GB50737-2011
GB50074-2002
GB50084-2001
GB5136.3-2003
GB5136.3-2003
GB50219-95
GB50316-2000
GB8163-1999
GB/T3092-1993
GB/T9119-2000
Reference standards:
GB/T17261-1998
GB50341-2003
HG21502.1-1992
HG21502.2-1992
Fire Prevention Design Code for Petrochemical Enterprises
Design Specification for Petroleum Reserve Tanks
Design Specification for Oil Storage Facilities
Automatic Sprinkler Fire Extinguishing System
Automatic Sprinkler Systems Part 3: Water Mist Nozzles
Automatic Sprinkler Systems Part 13: Water Curtain Nozzles
Code for Design of Water spray Fire Extinguishing System
Design Specification for Industrial Metal Piping
Seamless steel pipes for low-pressure fluid transportation
Welded steel pipes for low-pressure fluid transportation
Plate type flat welded steel pipe flange

Types and Basic Parameters of Steel Spherical Storage Tanks
Design Specification for Vertical Cylindrical Steel Welded Oil Tanks
Steel Vertical Cylindrical Fixed Top Storage Tank Series
Steel Vertical Cylindrical Internal Floating Roof Storage Tank Series

3、 Nozzle selection:
The nozzle should be selected from products that have been tested and approved by the National Quality Supervision and Inspection Center for Fixed Fire Extinguishing Systems and Refractory Components, and meet the design requirements.

4、 Water supply pressure:
Water pressure of water supply pipeline ≥ 0.65 MPa

5、 Anti corrosion treatment:
After prefabricated welding, the water supply riser, ring pipe, short section, flange, and fittings are subjected to hot-dip galvanizing and anti-corrosion treatment in sections, and the service life of the device reaches 20 years. Bolts, nuts, etc. are treated with electroplating zinc.

QPL-W spherical storage tank fire sprinkler extinguishing device
1、 Model representation:

储罐消防喷淋冷却装置(图1)
Indicate the volume of the storage tank
Indicate the water mist spray device
Indicate spherical tank spray

2、 Device schematic diagram:
储罐消防喷淋冷却装置(图2)
Schematic diagram of spherical storage tank fire water mist sprinkler fire extinguishing device
Instructions:
1. The device adopts a water mist nozzle with a rated pressure of 0.35MPa.
2. The water supply flow rate is ≤ 3m/s, and the water supply intensity is 9L/min · m2.
3. The distance between the nozzle and the tank wall is less than 700 (mm).
4. A filter should be installed in front of the device to prevent debris from blocking the nozzle and affecting the normal use of the device.
5
、It can be designed and produced according to the requirements of the spherical tank or the user.

3、 The basic configuration of the fire cooling water mist spray device for spherical storage tanks is shown in Table 1:
Model Spherical tank parameters Basic parameters of sprinkler system
Nominal volume
(m3)
Inner diameter D (mm) Water supply riser Environmental management spray nozzle
供水
method
pipe diameter
DN(mm)
number of layers
pipe diameter
DN(mm)
Ring diameter
(mm)
Nozzle model
(Flow rate, atomization angle)
quantity
a
QPL-W-650 650 10700 2 125 6 50 Φ1 11833 ZSTWA-30-120 116
Φ2 9061
Φ3 3665
QPL-W-1000 1000 12300 2 150 7 50/65 Φ 13936 ZSTWA-30-120 160
Φ1 12431
Φ2 8021
Φ3 3000
QPL-W-2000 2000 15700 2 175 9 50/65 Φ 17350 ZSTWA-30-120 240
Φ1 16278
Φ2 13251
Φ3 8719
Φ4 3000
QPL-W-3000 3000 18000 4 200 11 50/65/80 Φ 19700 ZSTWA-30-120 320
Φ1 18887
Φ2 16476
Φ3 12532
Φ4 7540
Φ5 3000
QPL-W-5000 5000 21200 4 200 13 50/65/80/100 Φ 22850 ZSTWA-30-120 476
Φ1 22150
Φ2 20130
Φ3 16875
Φ4 12674
Φ5 8010
Φ6 2614
QPL-W-6000 6000 22600 4 200 15 50/65/80/100 Φ 24304 ZSTWA-30-120 524
Φ1 23819
Φ2 22377
Φ3 20085
Φ4 17008
Φ5 13291
Φ6 9153
Φ7 4772

GPL-M cylindrical vertical (fixed top) storage tank fire cooling sprinkler system
1、 Model representation:

储罐消防喷淋冷却装置(图3)
Indicate the volume of the storage tank
Indicate the water curtain sprinkler system
Representing a cylindrical vertical (fixed top) storage tank

2、 Device schematic diagram:
储罐消防喷淋冷却装置(图4)
Schematic diagram of fire cooling water mist spray device for cylindrical vertical (fixed top) storage tank
Instructions:
1. The device adopts a water curtain nozzle, and the most unfavorable nozzle pressure is 0.10Mpa.
2. The water supply flow rate is ≤ 3m/s, and the water supply intensity is 2.5L/m · m2.
3. The distance between the nozzle and the tank wall is less than 700 (mm).
4. A filter should be installed in front of the device to prevent debris from blocking the nozzle and affecting the normal use of the device.
6. A spray ring pipe should be designed under the reinforced ring of the storage tank to ensure effective cooling of the tank wall.
7. Can be designed and produced according to storage tanks or user requirements.

3、 The basic configuration of the fire cooling water mist spray device for cylindrical vertical (fixed top) storage tanks is shown in

model Tank parameters Basic parameters of sprinkler system
Nominal volume
(m3)
inner diameter
(mm)
Can height
(mm)
Water supply riser Tank wall ring pipe Water curtain nozzle
Number of water supply routes pipe diameter
DN(mm)
number of layers Ring diameter
Ф(mm)
pipe diameter
DN(mm)
Nozzle specifications
(Flow coefficient X, spray angle)
quantity
Individual/layer
GPL-M-1000 1000 11500 10650 2 80 2 12700 Determine based on the protected area ZSTMB-TX/120 16
GPL-M-1500 1500 13500 11500 2 100 2 14700 Determine based on the protected area ZSTMB-TX/120 20
GPL-M-2000 2000 15780 11370 2 125 2 17180 Determine based on the protected area ZSTMB-TX/120 24
GPL-M-3000 3000 18900 11760 2 125 2 20100 Determine based on the protected area ZSTMB-TX/120 30
GPL-M-5000 5000 23700 12530 2 150 3 24900 Determine based on the protected area ZSTMB-TX/120 40
GPL-M-10000 10000 31000 14580 4 125 3 32200 Determine based on the protected area ZSTMB-TX/120 56
GPL-M-20000 20000 42000 17000 4 150 4 43200 Determine based on the protected area ZSTMB-TX/120 72
GPL-M-30000 30000 44000 20600 4 150 4 45200 Determine based on the protected area ZSTMB-TX/120 80
Note: The flow coefficient in the water curtain nozzle is determined by X based on different protection areas.
Table 2 Basic Parameters of Fire Cooling and Sprinkler System for Cylindrical Vertical (Fixed Top) Storage Tanks

FDG-M cylindrical vertical (inner floating roof) storage tank fire sprinkler cooling device
1、 Model representation:

储罐消防喷淋冷却装置(图5)
Indicate the volume of the storage tank
Indicate the water curtain sprinkler system
Representing a cylindrical vertical (inner floating roof) storage tank

2、 Device schematic diagram:
储罐消防喷淋冷却装置(图6)
Schematic diagram of fire cooling water curtain sprinkler system for cylindrical vertical (inner floating roof) storage tank
Instructions:
1. The device adopts a water curtain nozzle with a rated pressure of 0.35MPa
2. The water supply flow rate is 3m/s, and the water supply intensity is 2L/min · m2.
3. The distance between the nozzle and the tank wall is less than 700 (mm).
4. A filter should be installed in front of the device to prevent debris from blocking the nozzle and affecting the normal use of the device.
6. Spray ring pipes should be designed under the anti wind ring and reinforcement ring of the storage tank to ensure effective cooling of the tank wall.
7. Can be designed and produced according to storage tanks or user requirements.
3、 The basic configuration of the fire cooling water mist sprinkler system for cylindrical vertical (inner floating roof) storage tanks is shown in Table 3:

model Tank parameters Basic parameters of sprinkler system
Nominal volume
(m3)
inner diameter
(mm)
Can height
(mm)
Water supply riser Tank wall ring pipe Water curtain nozzle
Number of water supply routes pipe diameter
DN(mm)
number of layers Ring diameter
Ф(mm)
pipe diameter
DN(mm)
Nozzle specifications
(Flow coefficient X, spray angle)
quantity
Individual/layer
FPL-M-1000 1000 11500 12000 2 80 2 12700 Determine based on the protected area ZSTMB-TX/120 16
FPL-M-1500 1500 13000 13500 2 100 2 14200 Determine based on the protected area ZSTMB-TX/120 20
FPL-M-2000 2000 14500 14350 2 125 2 15700 Determine based on the protected area ZSTMB-TX/120 24
FPL-M-3000 3000 17000 15850 2 125 2 18200 Determine based on the protected area ZSTMB-TX/120 30
FPL-M-5000 5000 21000 16500 2 150 3 22200 Determine based on the protected area ZSTMB-TX/120 40
FPL-M-10000 10000 30000 16500 4 125 3 31200 Determine based on the protected area ZSTMB-TX/120 56
FPL-M-20000 20000 42000 17500 4 150 4 43200 Determine based on the protected area ZSTMB-TX/120 72
FPL-M-30000 30000 44000 20600 4 150 4 45200 Determine based on the protected area ZSTMB-TX/120 80
FPL-M-50000 50000 60000 19440 4 150 5 61200 Determine based on the protected area ZSTMB-TX/120 112
FPL-M-100000 100000 80000 21800 4 150 5 81200 Determine based on the protected area ZSTMB-TX/120 152
FPL-M-130000 130000 85000 25190 6 200 6 86200 Determine based on the protected area ZSTMB-TX/120 168
FPL-M-150000 150000 90000 26100 6 200 7 91200 Determine based on the protected area ZSTMB-TX/120 180
Note: The flow coefficient in the water curtain nozzle is determined by X based on different protection areas.
Table 3 Basic Parameters of Fire Cooling and Sprinkler System for Cylindrical Vertical (Internal Floating Roof) Storage Tanks