Specification Model
|
AERTO-600KGP33C
|
AERTO-800KGP33C
|
|
Rated capacity
|
600KVA/480KW
|
800KVA/640KW
|
|
input power
|
||
|
Input voltage waveform
|
pure sine wave
|
|
|
rated voltage
|
Three phase five wire system AC380V
|
|
|
voltage range
|
AC380V±25%
|
|
|
phase number
|
Three phase+N
|
|
|
rated frequency
|
50HZ; (customizable 60Hz)
|
|
|
Input power factor
|
≥ 0.99 (with DCU added)
|
|
|
frequency tracking
|
||
|
Frequency tracking range
|
50HZ±5%
|
|
|
Output frequency beyond the frequency tracking range
|
50HZ±0.01%
|
|
|
Frequency tracking efficiency
|
(0.5~2)Hz/s
|
|
|
soft start
|
0~**** 60s
|
|
|
output power supply
|
||
|
rated voltage
|
Three phase AC380V
|
|
|
Output voltage range
|
AC380V±1%
|
|
|
Voltage phase deviation
|
≤2°
|
|
|
Three-phase balance degree
|
1. Balance load voltage < ± 1%; |
|
|
waveform distortion
|
Sine wave, ≤ 3% under linear load; ≤ 6% under nonlinear loads |
|
|
overload capacity
|
Overload 120% for long-term operation, 125% can last for 10 minutes; Overload of 150% can last for 60 seconds |
|
|
crest factor
|
5:1
|
|
|
battery
|
||
|
rated voltage
|
DC672V
|
|
|
Battery Type
|
AERTO-2V or 12V maintenance free lead-acid battery
|
|
|
Standard configuration method
|
56 sections of 12V
|
|
|
Backup time
|
Optional at any time
|
|
|
system
|
||
|
Instant recovery time
|
<10ms
|
|
|
switch time
|
Mains ← → Battery: 0 ms; Mains ← → Bypass: ≤ 2 ms |
|
|
Protection, etc*
|
IP31 (customizable IP41) |
|
|
Power Efficiency |
≥90% |
|
|
ECO status |
≥97% |
|
|
Noise (1 meter away) |
<65dB |
|
|
Mean Time Between Failures (MTBF) |
450000 hours |
|
|
grounding resistance |
≤0.4Ω |
|
|
Grounding method |
TN-S standard |
|
|
communication interface |
RS-232; RS-485; (Can be customized with RJ-45 and WiFi; Bluetooth) |
|
|
cooling method |
Air cooling: forced air cooling mode
|
|
|
Box color |
Black, other colors can be customized |
|
|
environment
|
||
|
ambient temperature |
0℃ ~50℃ |
|
|
relative humidity |
≤ 95%, no condensation |
|
|
altitude |
<1500m |
|
|
Overall dimensions
|
||
|
Width x Depth x Height (mm) |
1000 × 800 × 1800 cabinet * 2 |
|
|
weight
|
|
|
|
Net quantity (Kg) |
3500
|
4000 |
Note: 1. The above data is for reference only. If there are any changes, the actual product shall prevail;
2. Redundant parallel operation;
3. We can customize special specification models according to customer needs.
- After adding WiFi function to this device, it can be operated and controlled using a mobile phone (Android operating platform) or IPA tablet, with a distance of ≤ 10m from the device;
- This machine can be equipped with RJ-45 for remote monitoring via Ethernet;
- This device can add wireless battery monitoring, which can monitor the battery voltage value, battery charging/discharging current, battery working temperature, battery capacity, and battery internal resistance in real time. At the same time, it can remotely operate and control battery fault alarms through wireless communication;