Uninterruptible power supply GP33 series 60KGP33C-160KGP33C
60KGP33C-160KGP33C
• High reliability design concept
• High reliability of operation
Strong environmental adaptability
High battery optimization performance
• Comprehensive and reliable protection
• Strong redundancy/additional redundancy parallel capability
Humanized network management
model | 60KGP33C | 80KGP33C | 100KGP33C | 120KGP33C | 150KGP33C | 160KGP33C |
capacity | 60KVA/48KW | 80KVA/64KW | 100KVA/80KW | 120KVA/96KW | 150KVA/120KW | 160KVA/128KW |
voltage | 380VAC/400VAC | |||||
input | ||||||
Input Voltage | 380VAC (or 400VAC) ± 25% three-phase four wire input | |||||
Input frequency range | 50/60Hz ± 5Hz automatic identification | |||||
power factor | >0.97 | |||||
*Large input current | 108A | 130A | 160A | 190A | 220A | 24** |
output | ||||||
output voltage | 380Vac ± 1% or 400Vac ± 1% | |||||
output frequency | Automatically track input frequency | |||||
Frequency stability (battery mode) | 50Hz±0.05% | |||||
Output waveform | sine wave | |||||
power factor | 0.8 | |||||
waveform distortion | Linear load<3%, non-linear load<5% | |||||
Peak factor | 3:1(max) | |||||
overload capacity | Can maintain 30 minutes/10 minutes/1 minute under overload of 110%/125%/150% | |||||
Convert time | ||||||
City power mode - battery mode | 0ms | |||||
bypass | ||||||
rated voltage | 380VAC(400VAC) | |||||
Bypass voltage range | 380VAC (400VAC) ± 20% (10%, 15%, and 20% adjustable) | |||||
rated frequency | 50/60Hz (automatic discrimination) | |||||
Bypass frequency range | ± 2% (adjustable from ± 1% to ± 5%) | |||||
battery | ||||||
Battery voltage (VDC) | 384 | 480 | ||||
panel display | ||||||
LED | Indicate input, inverter, bypass, battery status | |||||
LCD | Display input/output voltage, frequency, battery voltage, load percentage, and internal temperature | |||||
communication | ||||||
communication interface | Dry contact RS232 communication interface GM3101 interface | |||||
working environment | ||||||
Operating temperature | 0~40℃ | |||||
relative humidity | 0~95% non condensing | |||||
Storage temperature | -25℃~55℃ | |||||
noise | <65dB |
<70dB
| ||||
physical properties | ||||||
**Protection | Overload, deep discharge and overcharge protection | |||||
物理性能 | ||||||
Dimensions: Width * Depth * Height (mm) | 570*705*1250 | 710*840*1260 | 1100*850*1380 | |||
Net weight (Kg) | 497 | 556 | 756 | 901 | 1200 | 1300 |
Gross weight (Kg) | 574 | 633 | 856 | 1001 | 1300 | 1400 |
option | Parallel module, harmonic filter, input isolation transformer, intelligent monitoring software, SNMP adapter | |||||
**Standard | EN50091-1 EN50091-2 Class A | |||||
execution standard | YD/T1095-2000 | |||||
Aiyat is committed to technological innovation. If there are any changes to the current product specifications, no further notice will be given. The actual product shall prevail.