Phone
13168669833
-
Address
5th Floor, Taifenghui, No. 33 Huawei Road, Xiangzhou District, Zhuhai City, Guangdong Province
Zhuhai Kemet Electronics Co., Ltd
13168669833
5th Floor, Taifenghui, No. 33 Huawei Road, Xiangzhou District, Zhuhai City, Guangdong Province
Brand: British Standard BST
Model: BT751
Download: BT751 Product Documentation. pdf
British Standard BST-BT751 Insulation Resistance Tester with Voltage Measurement Function
BST-BT751 is a portable insulation resistance tester designed specifically for electrical installation personnel to measure insulation resistance. It can measure voltages up to 1000VDC and 600V, and perform continuity tests on grounding conductors. It is suitable for both civilian and industrial electrical environments.
Other special features include LOCK lock function, adjustable timer, and a large LCD backlit display screen. The LOCK locking function can perform continuous insulation measurement on the tested equipment. The adjustable timer from 2s to 60s allows users to decide the duration of the measurement, and its large LCD display with backlight function allows users to work in weak/dim light environments.
| display | 4-digit LCD maximum value 9999 with units and symbols |
| Sample Rate | Standard mode: 0.15mm ² to 240mm ² |
| memory | data hold |
| Working humidity | <70% RH |
| operation temperature | 0 ° C to 40 ° C |
| Storage humidity | <75% RH |
| storage temperature | -10 ° C to 60 ° C |
| weight | Approximately 450g (including battery) |
| Type | 6 units of 1.5V – 1.5V – LR6 – AA – AM3 – MN 1500 |
| BATTERY LIFE | Typical 50 hours (multimeter mode); Typical 1000 insulation tests |
| sleep mode | No operation for 10 minutes |
| External dimensions | 74 (W) x 135 (H) x 30 (D) mm. |
AC voltage
|
Gear position |
resolution |
accuracy |
Input impedance |
overload protection |
|
0.1~600.0V |
0.1V |
(0.8% rdg +4 dgt) |
3MΩ |
605 VAC max RMS |
Maximum peak factor √ 2
DC Voltage
|
Gear position |
resolution |
accuracy |
Input impedance |
overload protection |
|
0.1~600.0V |
0.1V |
(0.5% rdg +1 dgt) |
3MΩ |
605 VAC max RMS |
On Off Test
|
Gear position |
resolution |
accuracy |
overload protection |
|
0.1 – 199.9 Ohm |
0.1 Ohm |
+/- (2.0% rdg + 3 dgt) |
605V AC max RMS per 1 minute |
When the resistance is below 30 OHM, the peak beeps
Low resistance measurement LO Ohm: Continuity of protection conductors
|
Gear position |
resolution |
accuracy |
overload protection |
|
0.01 – 19.99 Ohm |
0.01 Ohm |
+/- (2.0% rdg + 3 dgt) |
605V max RMS |
Test current:>200mA DC up to 5 Ohm (including test wiring resistance)
Test current:>45mA DC over 5 Ohm (including test wiring resistance)
Open circuit voltage: 4<V0<24V
Insulation resistance measurement M Ohm: Insulation resistance (Auto Range)
|
testing voltage |
Gear Position (OHM) | Resolution (OHM) | accuracy |
overload protection |
|
250V |
0.001 – 0.100M |
0.001M |
+/- 10 dgt |
605V max RMS |
|
0.101 – 3.999M |
0.001M |
+/- (2.0% rdg + 5 dgt) |
||
|
4.00- 39.99M |
0.01 M |
|||
|
40.0 – 399.9M |
0.1 M |
+/- (5.0% rdg + 5 dgt) |
||
|
400 ¡V1000M |
1M |
|||
|
500V |
0.001 – 0.250M |
0.001M |
+/- 15 dgt |
|
|
0.251 – 3.999M |
0.001M |
+/- (2.0% rdg + 5 dgt) |
||
|
4.00- 39.99M |
0.01 M |
|||
|
40.0 – 399.9M |
0.1M |
|||
|
400- 2000M |
1M |
+/- (5.0% rdg + 5 dgt) |
||
|
1000V |
0.001 – 0.250M |
0.001M |
+/- 15 dgt |
|
|
0.251 – 3.999M |
0.001M |
+/- (2.0% rdg + 5 dgt) |
||
|
4.00- 39.99M |
0.01 M |
|||
|
40.0 – 399.9M |
0.1M |
|||
|
400 – 1000M |
1M |
+/- (3.0% rdg + 5 dgt) |
||
|
1000 – 4000M |
1M |
+/- (5.0% rdg + 10 dgt) |