HZD-W/L wall mounted dual channel vibration monitoring and protection device
lImplement intelligent processing: alarmThe values of I and II can be set arbitrarily through the panel buttons
lThe panel buttons can adjust the range value without the need for potentiometer adjustment, making it convenient for on-site debugging
lIf you don't press the operation key for one minute, you can return to the running state by yourself
lAlarm delay adjustment range1~60Seconds to prevent false alarms caused by on-site interference
lIt has power up and power down detection functions, sensor disconnection detection functions, and can effectively suppress instrument false alarms by cutting off alarm and shutdown output circuits
l(Long press)◄key)The vibration intensity and amplitude can be freely switched.
HZD-W/L wall mounted dual channel vibration monitoring and protection device
lFrequency range:10~300Hz
lquantity Cheng:0~50.0mm/s 0~500um 020.0mm/s 0~200um
laccurate indeed Degree:±1%(Full scale)
lCurrent output: 4~20mA
lSwitching output:DC 30V/ 5AorAC250V/5ANormally Open
lAlarm setting: Any setting within the full range
lEnvironmental temperature: During operation:0~65When stored at ℃:-30~80℃
lRelative humidity: to95%Not condensing
lPower supply voltage:220VAC/50Hz±10%
lOverall dimensions:240×190mm
l Installation method: Wall mounted
lInstallation hole position size:275(Long)×170(Width) unitmm(Hole diameter)5mm)

HZD-W/L Dual Channel Vibration Monitoring and Protection InstrumentInstalled in the control room, insert the monitoring device from the front of the control room during installation, then install the left and right mounting brackets (provided by the manufacturer) from the back, and tighten the screws. Connect the input and output wires to the back terminal board of the monitoring device as required.
The wall mounted monitoring instrument can be installed on the wall on site or on a centralized wall. Simply drill holes on the wall according to the installation holes behind the monitor to fix it.