Low smoke halogen-free fire-resistant power cable

NegotiableUpdate on 12/19
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
Low smoke halogen-free fire-resistant power cables have high fire resistance performance and can withstand direct flame combustion without short circuits or faults for a certain period of time. Therefore, in the event of a fire, it is beneficial to reduce losses.
Product Details

Low smoke halogen-free fire-resistant power cable

Product execution standard Q/LB2006.2

Fire resistance characteristics meet the requirements of GB12666.6-90 (IEC331)

Product features and uses: This product has high fire resistance and can withstand direct flame combustion without short circuits or short circuit faults for a certain period of time. Therefore, in the event of a fire, it is beneficial to reduce losses. Low smoke halogen-free cables are environmentally friendly cables, especially suitable for industries such as power, large buildings, railways, ships, etc. that require high fire safety requirements.


Usage characteristics:

1. Rated AC voltage: U0/U 0.6/1KV

2. High long-term working temperature: flame retardant polyvinyl chloride J-edge and sheath 70 ℃ and 105 ℃

Fluoroplastic J-edge and sheath at 200 ℃ and 260 ℃

Cross linked polyethylene J edge at 90 ℃

Low smoke halogen-free flame-retardant polyolefin at 70 ℃

Low smoke halogen-free flame-retardant cross-linked polyolefin at 90 ℃ and 120 ℃

3. Low ambient temperature: flame retardant polyvinyl chloride sheath: fixed installation -40 ℃, non fixed installation -15 ℃

Fluoroplastic J-edge and sheath: fixed installation -60 ℃; Non fixed laying -20 ℃

4. Fire resistance characteristics:

Compliant with IEC331 regulations Flame temperature 750 ℃, combustion time 3h, cooling time 12h, additional rated voltage, additional 3A current
Compliant with GB12666.6-A Flame temperature 950-1000 ℃, combustion time 90min, additional rated voltage 3A current
Compliant with GB12666.6-B class Flame temperature 750-800 ℃, combustion time 90min, additional rated voltage 3A current

5. The temperature for cable installation and laying shall not be lower than 0 ℃

6. Recommended allowable bending radius for laying: Non armored cables shall not be less than 6 times the outer diameter of the cable

Armored cable not less than 12 times the outer diameter of the cable

Fluoroplastic insulation and sheath material cables shall not be less than 8 times the outer diameter of the cable


Low smoke halogen-free fire-resistant power cableFor more cables, please contact us!