The protection circuit of the OBO multifunctional lightning protection socket CNS 3-D-PRC is composed of gas discharge tubes and varistors, and is continuously monitored through a built-in temperature fuse. When the green LED lights up, it indicates that the lightning protection socket is in good condition. If there is a fault, the red LED will light up and the green LED will turn off, accompanied by a long sound signal to remind relevant maintenance personnel to replace the lightning protection socket. The CNS 3-D testing was conducted in accordance with VDE0675/Part 6 (Draft 11.89) and has also passed CE safety certification. CNS 3-D has multiple national standard plugs and sockets to choose from.
CNS 3-D-PRCLightning protection socket functionThe protection circuit of the OBO multifunctional lightning protection socket CNS 3-D-PRC is composed of gas discharge tubes and varistors, and is continuously monitored through a built-in temperature fuse. When the green LED lights up, it indicates that the lightning protection socket is in good condition. If there is a fault, the red LED will light up and the green LED will turn off, accompanied by a long sound signal to remind relevant maintenance personnel to replace the lightning protection socket. The CNS 3-D testing was conducted in accordance with VDE0675/Part 6 (Draft 11.89) and has also passed CE safety certification. CNS 3-D has multiple national standard plugs and sockets to choose from.
CNS 3-D-PRCApplication of lightning protection socketsCNS 3-D-PRC D-level power lightning protection socket is a precision power protection product specially designed and manufactured for electronic terminal equipment. At the same time, three types of terminal devices can be protected together.
CNS 3-DTechnical parameters of lightning protection socket
| CNS 3-D-PRC lightning protection socket device |
| Nominal voltage UN |
230V ~ |
| Maximum operating voltage Umax~ |
250V ~ |
| Rated current IN |
13A |
| Rated discharge current In (8/20) |
2.5KA |
| Maximum output power Pmax |
3600W |
| Maximum discharge current Imax (8/20) |
7KA |
Residual pressure under Ures L-N Clock L/N-PE |
≤1.0KV ≤1.5KV |
| Response time tA |
< 25ns |
| Maximum ground wire connection diameter q |
2.5mm² |
| color |
black |
size Plug W * H Multiple sockets L * W * H Connection line length L |
57*74mm 260*60*40mm 2.0m |
CNS 3-D-PRCInstallation of lightning protection socketsThe installation of CNS 3-D-PRC is very simple, just plug its plug directly into the socket on the circuit, and then plug the device into the socket of CNS 3-D-PRC.
Attention: Ensure that the lightning protection socket has good grounding.