The V10-C series surge protector is designed according to the requirements of IEC61643 and IEC60364, and the device complies with DINVDE0675Part6 (Draft 11.89) A1 and A2, with a grade of C+D.
The V10-C series surge protector is designed according to the requirements of IEC61643 and IEC60364, and the device complies with DINVDE0675Part6 (Draft 11.89) A1 and A2, with a grade of C+D.
V10-C is used for induction lightning protection of sensitive electronic equipment in buildings, and can be used as a second level power line surge protector in buildings with lightning protection levels of III and IV. It is installed in the distribution cabinet at the junction of LPZ1 and LPZ2, and LPZ2 and LPZ3 zones inside the building.
If the lightning arrester is damaged due to overload, the built-in circuit breaker will promptly operate, interrupt the connection with the power supply, and the color of the fault indication display window will change from green to red.
V10-CCharacteristics and advantages of lightning arrester
| feature |
Advantages of use |
| Metal oxide varistor |
Lightning arresters can handle frequent actions and have a long lifespan |
| Equipped with a working status indicator light |
Safe to use, the working status of the lightning arrester is clear at a glance |
| compact design |
Save installation space |
| Adopting a 3+1 structure |
Suitable for multiple power supply systems |
V10-CTechnical parameters of lightning arrester
| model |
V10-C/0 |
V10-C/2 |
V10-C/3 |
V10-C/4 |
V10-C/3+NPE |
| According to the classification level of VDEO675 Part 6 |
C+D category |
| protected mode |
|
L-PE、N-PE |
L-PE |
L-PE、N-PE |
L-N、N-PE |
| Maximum continuous operating voltage Uc |
385V~ |
| Lightning protection zone LPZ |
1 → 2 or 2 → 3 |
| Nominal discharge current (8/20 μ s) In |
10KA |
20KA |
30KA |
40KA |
30KA |
| Maximum discharge current (8/20 μ s) Imax |
20KA |
40KA |
60KA |
80KA |
60KA |
| Voltage protection level Up |
≤1.8KV |
| Response time Ta |
<25ns |
| Maximum backup fuse with short-circuit withstand capacity of 25KA |
125A gl/gG |
| Working temperature range |
-40 ℃ to+80 ℃ |
| protection level |
According to EN50052, fixed on a 35mm guide rail |
| Installation method |
2.5-35mm2 (single strand, multi strand wire) |
| I Protection Level |
IP 20 |
| Connecting wire cross-sectional area single/multiple/multiple flexible wires |
2.5-25mm2 (multi strand flexible wire with protective sheath at the connection end) |