V10-C is designed according to the requirements of IEC61643 and IEC60364, and is used for inductive lightning protection of sensitive electronic devices in buildings. It can be used as a second level power line surge protector in buildings with lightning protection levels of III and IV. If the lightning arrester is damaged due to overload, the built-in circuit breaker will act in a timely manner, interrupting the connection with the power supply, and the color of the fault indicator display window will change to red.
Function&Features:V10-C is designed according to the requirements of IEC61643 and IEC60364, and is used for inductive lightning protection of sensitive electronic devices in buildings. It can be used as a second level power line surge protector in buildings with lightning protection levels of III and IV. If the lightning arrester is damaged due to overload, the built-in circuit breaker will act in a timely manner, interrupting the connection with the power supply, and the color of the fault indicator display window will change to red.
Technical Specifications:
| model |
V10-C/0 |
V10-C/2 |
V10-C/3 |
V10-C/4 |
V10-C/3+NPE |
According to VDE0675 Part 6 Classification level |
Class C |
| Rated voltage |
- |
L/N-PE |
L-PEN |
L/N-PE |
L-N、N-PE |
| Maximum continuous operating voltage |
385V |
| Nominal discharge current (8/20 μ s) |
10KA |
20KA |
30KA |
40KA |
30KA |
| Maximum discharge current (8/20 μ s) |
20KA |
40KA |
60KA |
80KA |
60KA |
| Voltage protection level |
≤1.8KV |
| Maximum backup fuse short-circuit withstand voltage 25KArpm |
125A gl/gG |
| response time |
﹤25ns |
| Working temperature range |
-40 ℃ to+80 ℃ |
| Connecting wire cross-sectional area |
2.5-35m ㎡ |
| IP rating |
IP20 |
| material |
Polyimide 6 |
| Installation method |
Fixed on a 35mm wide guide rail according to EN 50022 |