PT100/PT1000/thermocouple eight channel temperature control instrument (capable of outputting RS485 and independent control)

NegotiableUpdate on 11/18
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The YY-F860 instrument is an eight channel intelligent temperature control instrument that can be simultaneously equipped with 8 sensors PT100/PT1000 temperature sensors and K, J, R, S thermocouples. It has an independent self-tuning mode and independent PID parameters, and can accurately control the 8 temperature channels. It can communicate with a computer RS485 serial port or drive micro printing timing. The communication protocol adopts the internationally recognized Modbus RTU protocol, which can form a centralized control management system with PC, PLC or touch screen, better meeting the needs of customers in various complex and changing environments. It is widely used in industries such as automobiles, airports, computer rooms, food and drug production, etc.

Product Details

PT100/PT1000/thermocouple eight channel temperature control instrument (capable of outputting RS485 and independent control)

PT100/PT1000/热电偶八通道温度控制仪器

1、 Technical performance
1. Input types: CU50 (-50.0-150.0 ℃), Pt100 (-199-600.0 ℃), Pt1000 (-199-600.0 ℃)
K(0~1300℃)、E(0~700.0℃)、J(0~900.0℃)、S(0~1600℃)
Note 1: When the user places an order specifying input signals of 0-5V and 1-5V analog signals, the instrument no longer supports the input of various thermocouple and thermistor signals mentioned above,
Note 2: This instrument is a multi-channel instrument that can connect multiple sensors. But isolated sensors must be selected. Taking a thermocouple as an example: both wires of the thermocouple
Cannot conduct with metal casing. Otherwise, there may be situations such as inaccurate temperature measurement.
2. Control methods: Two position control, PID control
3. Output mode: Relay 240V 5A (resistive load) Solid state relay trigger signal 20MA/9V
4. Measurement accuracy: ± 0.5F • S ± 1 word, additional cold end calibration error ± 1 ℃
5. Working power supply: AC220V 50Hz Power consumption: less than 5W
6. Working environment: 0~50 ℃, relative humidity ≤ 85% RH, non corrosive and non strong electromagnetic radiation environment
7. Dimensions: 160 × 80 × 120 Hole size: 152 × 76

2、 Instrument panel


PT1000/热电偶八通道温度控制仪器
3、 Instrument wiring (for reference only, based on the wiring diagram on the instrument)



PT100八通道温度控制仪器

Note: When communicating via RS485, the instrument should be connected to 'VA+' and 'VB -';

4、 Instrument usage

1First level menu settings

Press the function key(SETKey)3In seconds, enter the first level menu, and at this point, '...'1Road display window 'and' Section '2The 'Road Display Window' displays parameter symbols and values respectively. You can press the ◄ (cursor shift key), ▲ (plus key), and ▼ (minus key) keys to change the parameter values. After the modification is complete, pressSETSave key to enter the next parameter; Modify other parameters using the same method.

2Secondary menu settings

Each channel parameter is adjusted according toCH1TheCH2TheCH3TheCH4TheCH5TheCH6TheCH7TheCH8Three seconds to enter the corresponding channel menu item, then press the ◄, ▲, ▼ keys to change the parameter values. After completing the modification, pressSETSave key to enter the next parameter; The parameters are shown in the table below:

Primary Menu,Press the function key(SETKey)3Enter in seconds

serial number

prompt

Storage address

name

set the scope

Instructions

factory default

one

level

dish

single

0

LOCK

0000H

combination lock

050

Password lock is18When allowed to modify all

Parameter, not for18It is prohibited to modify all parameters at this time

18

1

Sn

0001H

Enter specifications

04

CU50ThePtTheKTheETheJTheS

K

2

t

0002H

Output cycle

0120 S

Set the action cycle for relay control

20 S

3

dp

0003H

decimal point position

01

0. No decimal point; 1.There is a decimal point

0

4

DIL

0004H

Lower limit of set value

Range starting point~DIH

This parameter limits the lower limit of the set value

random

5

DIH

0005H

Set the upper limit of the value

DIL~Full range

This parameter limits the upper limit of the set value

random

6

OPB

0006H

Secondary output mode

02

0.No output

1.openRS485Serial communication function

0

7

Add

0007H

Mailing Address

164

The numbering of instruments in the centralized control system

1

8

bt

0008H

communication baud rate

03

01200 12400

24800 39600

9600

submenu,pressCH1key3Enter in seconds 1Channel menu

two

level menu

one

Channel parameter setting

9

SU1

0009H

1Channel control point setting

Scope byDIHTheDILdecide

1Channel control point temperature setting parameters

random

10

AL1

000AH

Alarm setting value

Scope byDIHTheDILdecide

fromALP1Parameters determine the alarm mode

For details, seeALP1Parameter Description

0

11

SC1

000BH

Error correction value

±20.0

Translation correction value of sensor error

0

12

P1

000CH

Proportional band

0200.0

adoptPIDWhen controlling, the proportional band determines the magnitude of the system's proportional gain, PThe larger,

The smaller the effect of proportion,The smaller the overshoot,But being too small will increase the heating time.

(P=0At this time, the instrument will switch to two position control,Some actuators that are not suitable for frequent start-up, such as fans, compressors, motors, etc., should use this method. Please refer to the parameters for detailsHY1The explanation section)

15.0

13

I1

000DH

integration time

03000

Set the integration time to release proportional control

The residual deviation that occurred,Too much will delay the time for the system to reach equilibrium,Too small can cause fluctuations

240

14

D1

000EH

Differential time

0200S

Set differential time to prevent output waves

move,Improve the stability of control

30

15

Hy1

000FH

Main control and alarm return difference

0.150.0

When the instrument is a two position control (proportional band)P=0)The dead zone between the opening or closing of the actuator to avoid frequent actions of the actuator.

When the main control is in heating mode:

When measuring valuesPV1≤ Set valueSV1-HY1When the actuator opens, whenPV1SV1+HY1When, the actuator closes.

1.0

16

At1

0010H

Self-tuning parameters

01

0OFFDisable auto-tuning 1OnStart self-tuning

0

17

CoL1

0011H

Selection of heating and cooling methods

01

0Heating function 1Cooling function

0

18

ALP1

0012H

Alarm definition

06

0: No alarm; 1: Upper limit alarm

2: Lower limit alarm;3:Upper deviation alarm

4Deviation alarm 5Alarm outside the interval

6Alarm reported within the interval

1

Press separatelyCH2/CH3/CH4/CH5/CH6/CH7Press the key to enter2-7Channel menu,Set up using the same method

pressCH8key3Enter in seconds 8Channel menu

two

Channel parameter setting

79

SP8

004FH

Ditto.

80

AL8

0050H

Ditto.

81

SC8

0051H

Ditto.

82

P8

0052H

Ditto.

83

I8

0053H

Ditto.

84

D8

0054H

Ditto.

85

Hy8

0055H

Ditto.

86

At8

0056H

Ditto.

87

CoL8

0057H

Ditto.

88

ALP8

0058H

Ditto.

Note: Please refer to the "Communication Protocol" section later for the measurement value addresses of each channel.

6、 Self tuning operation

First, set the settings and then enter the menuSet the hysteresis to around 0.5-1, set AT to ON, and the instrument enters a self-tuning state. The corresponding display window flashes and displays the "AT" character. At this time, the instrument is in positional control. After three oscillations, the instrument determines new parameters such as P, I, D and saves them, and resets to the control state.

7、 Error message

1. When the instrument window displays "HH or LL", please check if the sensor wiring is correct.

2. When it is found that the temperature between channels is unstable due to mutual influence, please check whether the equipped sensor is an isolated type.