PT100/PT1000/thermocouple eight channel temperature control instrument (capable of outputting RS485 and independent control)
1、 Technical performance
1. Input types: CU50 (-50.0-150.0 ℃), Pt100 (-199-600.0 ℃), Pt1000 (-199-600.0 ℃)
K(0~1300℃)、E(0~700.0℃)、J(0~900.0℃)、S(0~1600℃)
Note 1: When the user places an order specifying input signals of 0-5V and 1-5V analog signals, the instrument no longer supports the input of various thermocouple and thermistor signals mentioned above,
Note 2: This instrument is a multi-channel instrument that can connect multiple sensors. But isolated sensors must be selected. Taking a thermocouple as an example: both wires of the thermocouple
Cannot conduct with metal casing. Otherwise, there may be situations such as inaccurate temperature measurement.
2. Control methods: Two position control, PID control
3. Output mode: Relay 240V 5A (resistive load) Solid state relay trigger signal 20MA/9V
4. Measurement accuracy: ± 0.5F • S ± 1 word, additional cold end calibration error ± 1 ℃
5. Working power supply: AC220V 50Hz Power consumption: less than 5W
6. Working environment: 0~50 ℃, relative humidity ≤ 85% RH, non corrosive and non strong electromagnetic radiation environment
7. Dimensions: 160 × 80 × 120 Hole size: 152 × 76
2、 Instrument panel
Note: When communicating via RS485, the instrument should be connected to 'VA+' and 'VB -';
4、 Instrument usage1First level menu settings
Press the function key(SETKey)3In seconds, enter the first level menu, and at this point, '...'1Road display window 'and' Section '2The 'Road Display Window' displays parameter symbols and values respectively. You can press the ◄ (cursor shift key), ▲ (plus key), and ▼ (minus key) keys to change the parameter values. After the modification is complete, pressSETSave key to enter the next parameter; Modify other parameters using the same method.
2Secondary menu settings
Each channel parameter is adjusted according toCH1TheCH2TheCH3TheCH4TheCH5TheCH6TheCH7TheCH8Three seconds to enter the corresponding channel menu item, then press the ◄, ▲, ▼ keys to change the parameter values. After completing the modification, pressSETSave key to enter the next parameter; The parameters are shown in the table below:
|
Primary Menu,Press the function key(SETKey)3Enter in seconds |
|||||||||
|
serial number |
prompt |
Storage address |
name |
set the scope |
Instructions |
factory default |
|||
|
one level dish single |
0 |
LOCK |
0000H |
combination lock |
0~50 |
Password lock is18When allowed to modify all Parameter, not for18It is prohibited to modify all parameters at this time |
18 |
||
|
1 |
Sn |
0001H |
Enter specifications |
0~4 |
CU50ThePtTheKTheETheJTheS |
K |
|||
|
2 |
t |
0002H |
Output cycle |
0~120 S |
Set the action cycle for relay control |
20 S |
|||
|
3 |
dp |
0003H |
decimal point position |
0~1 |
0. No decimal point; 1.There is a decimal point |
0 |
|||
|
4 |
DIL |
0004H |
Lower limit of set value |
Range starting point~DIH |
This parameter limits the lower limit of the set value |
random |
|||
|
5 |
DIH |
0005H |
Set the upper limit of the value |
DIL~Full range |
This parameter limits the upper limit of the set value |
random |
|||
|
6 |
OPB |
0006H |
Secondary output mode |
0~2 |
0.No output 1.openRS485Serial communication function |
0 |
|||
|
7 |
Add |
0007H |
Mailing Address |
1~64 |
The numbering of instruments in the centralized control system |
1 |
|||
|
8 |
bt |
0008H |
communication baud rate |
0~3 |
0:1200; 1:2400; 2:4800; 3:9600 |
9600 |
|||
|
submenu,pressCH1key3Enter in seconds 1Channel menu |
|||||||||
|
two level menu
one Channel parameter setting |
9 |
SU1 |
0009H |
1Channel control point setting |
Scope byDIHTheDILdecide |
1Channel control point temperature setting parameters |
random |
||
|
10 |
AL1 |
000AH |
Alarm setting value |
Scope byDIHTheDILdecide |
fromALP1Parameters determine the alarm mode For details, seeALP1Parameter Description |
0 |
|||
|
11 |
SC1 |
000BH |
Error correction value |
±20.0 |
Translation correction value of sensor error |
0 |
|||
|
12 |
P1 |
000CH
|
Proportional band |
0~200.0 |
adoptPIDWhen controlling, the proportional band determines the magnitude of the system's proportional gain, PThe larger, The smaller the effect of proportion,The smaller the overshoot,But being too small will increase the heating time. (P=0At this time, the instrument will switch to two position control,Some actuators that are not suitable for frequent start-up, such as fans, compressors, motors, etc., should use this method. Please refer to the parameters for detailsHY1The explanation section) |
15.0 |
|||
|
13 |
I1 |
000DH |
integration time |
0~3000 |
Set the integration time to release proportional control The residual deviation that occurred,Too much will delay the time for the system to reach equilibrium,Too small can cause fluctuations |
240 |
|||
|
14 |
D1 |
000EH |
Differential time |
0~200S |
Set differential time to prevent output waves move,Improve the stability of control |
30 |
|||
|
15 |
Hy1 |
000FH |
Main control and alarm return difference |
0.1~50.0 |
When the instrument is a two position control (proportional band)P=0)The dead zone between the opening or closing of the actuator to avoid frequent actions of the actuator. When the main control is in heating mode: When measuring valuesPV1≤ Set valueSV1-HY1When the actuator opens, whenPV1≥SV1+HY1When, the actuator closes. |
1.0 |
|||
|
16 |
At1 |
0010H |
Self-tuning parameters |
0~1 |
0:OFFDisable auto-tuning 1:OnStart self-tuning |
0 |
|||
|
17 |
CoL1 |
0011H |
Selection of heating and cooling methods |
0~1 |
0Heating function 1Cooling function |
0 |
|||
|
18 |
ALP1 |
0012H |
Alarm definition |
0~6 |
0: No alarm; 1: Upper limit alarm 2: Lower limit alarm;3:Upper deviation alarm 4Deviation alarm 5Alarm outside the interval 6Alarm reported within the interval |
1 |
|||
|
Press separatelyCH2/CH3/CH4/CH5/CH6/CH7Press the key to enter2-7Channel menu,Set up using the same method |
|||||||||
|
pressCH8key3Enter in seconds 8Channel menu |
|||||||||
|
two Channel parameter setting |
79 |
SP8 |
004FH |
Ditto. |
|
|
|
||
|
80 |
AL8 |
0050H |
Ditto. |
|
|
|
|||
|
81 |
SC8 |
0051H |
Ditto. |
|
|
|
|||
|
82 |
P8 |
0052H |
Ditto. |
|
|
|
|||
|
83 |
I8 |
0053H |
Ditto. |
|
|
|
|||
|
84 |
D8 |
0054H |
Ditto. |
|
|
|
|||
|
85 |
Hy8 |
0055H |
Ditto. |
|
|
|
|||
|
86 |
At8 |
0056H |
Ditto. |
|
|
|
|||
|
87 |
CoL8 |
0057H |
Ditto. |
|
|
|
|||
|
88 |
ALP8 |
0058H |
Ditto. |
|
|
|
|||
Note: Please refer to the "Communication Protocol" section later for the measurement value addresses of each channel.
6、 Self tuning operation
First, set the settings and then enter the menu,Set the hysteresis to around 0.5-1, set AT to ON, and the instrument enters a self-tuning state. The corresponding display window flashes and displays the "AT" character. At this time, the instrument is in positional control. After three oscillations, the instrument determines new parameters such as P, I, D and saves them, and resets to the control state.
7、 Error message
1. When the instrument window displays "HH or LL", please check if the sensor wiring is correct.
2. When it is found that the temperature between channels is unstable due to mutual influence, please check whether the equipped sensor is an isolated type.