PT100/PT1000/thermocouple six channel temperature control instrument (can be equipped with RS485)

NegotiableUpdate on 11/18
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The YY-F660 instrument is a six channel intelligent temperature control instrument that can be simultaneously equipped with six PT100/PT1000 temperature sensors and K, J, R, and S-type thermocouples. It has an independent self-tuning mode and independent PID parameters, and can accurately control the six temperature channels. It can communicate with a computer RS485 serial port or drive micro printing timing. The communication protocol adopts the internationally recognized Modbus RTU protocol, which can form a centralized control and management system with PCs, PLCs, or touch screens. It can better meet the needs of customers in various complex and changing environments, and is widely used in industries such as automobiles, airports, computer rooms, food and drug production, etc.

Product Details

PT100/PT1000/thermocouple six channel temperature control instrument (can be equipped with RS485)

PT1000六通道温度控制仪器表

1、 Technical performance
1. Input types: CU50 (-50.0-150.0 ℃), Pt100 (-199-600.0 ℃), Pt1000 (-199-600.0 ℃)
K(0~1300℃)、E(0~700.0℃)、J(0~900.0℃)、S(0~1600℃)
Note 1: When the user places an order specifying input signals of 0-5V and 1-5V analog signals, the instrument no longer supports the input of various thermocouple and thermistor signals mentioned above,
Note 2: This instrument is a multi-channel instrument that can connect multiple sensors. But isolated sensors must be selected. Taking a thermocouple as an example: both wires of the thermocouple
Cannot conduct with metal casing. Otherwise, there may be situations such as inaccurate temperature measurement.
2. Control methods: Two position control, PID control
3. Output mode: Relay 240V 5A (resistive load) SSR trigger signal 20ma/9V
4. Measurement accuracy: ± 0.5F • S ± 1 word, additional cold end calibration error ± 1 ℃
5. Working power supply: AC220V 50Hz Power consumption: less than 5W
6. Working environment: 0~50 ℃, relative humidity ≤ 85% RH, non corrosive and non strong electromagnetic radiation environment
7. Dimensions: 160 × 80 × 120 Hole size: 152 × 76 (mm)
2、 Instrument panel

6路PT100智能数显仪表

3、 Instrument wiring (for reference only, based on the wiring diagram on the instrument)

六通道智能温控仪表



Note: When communicating via RS485, the instrument should be connected to 'VA+' and 'VB -';

4、 Instrument usage

1. First level menu settings

Press the function key (SET key) for 3 seconds to enter the first level menu. At this time, the 'First Display Window' and 'Second Display Window' will display parameter symbols and values respectively. You can press the ◄ (cursor shift key), ▲ (plus key), and ▼ (minus key) keys to change the parameter values. After the modification is complete, press the SET key to save and enter the next parameter; Modify other parameters using the same method.

2. Secondary menu settings

Press CH1, CH2, CH3, CH4, CH5, and CH6 for three seconds to enter the corresponding channel menu items for each channel parameter. Then press the ◄, ▲, and ▼ keys to change the parameter values. After completing the modification, press the SET key to save and enter the next parameter; The parameters are shown in the table below:

First level menu, press the function key (SET key) for 3 seconds to enter

serial number

prompt

Storage address

name

set the scope

Instructions

factory default

one

level

dish

single

0

LOCK

0000H

combination lock

0~50

When the password lock is set to 18, all modifications are allowed

Parameters are prohibited from being modified unless they are set to 18

18

1

Sn

0001H

Enter specifications

0~5

CU50ThePtTheKTheETheJTheS

K

2

t

0002H

Output cycle

0~120 S

Set the action cycle for relay control

20 S

3

dp

0003H

decimal point position

0~1

0. No decimal point; 1. There is a decimal point

0

4

DIL

0004H

Lower limit of set value

Range starting point~DIH

This parameter limits the lower limit of the set value

random

5

DIH

0005H

Set the upper limit of the value

DIL~Full range

This parameter limits the upper limit of the set value

random

6

OPB

0006H

Secondary output mode

0~2

0.noneoutput

1.openRS485 serial communicationfunction

0

7

Add

0007H

communicationaddress

1~64

The numbering of instruments in the centralized control system

1

8

bt

0008H

communicationBaud rate

0~3

0:1200; 1:2400;

2:4800;3:9600

9600

Secondary menu, press CH1 key for 3 seconds to enter 1Channel menu

two

level menu

one

Channel parameter setting

9

SP1

0009H

1-channel control point setting

Scope byDILTheDIHdecide

Temperature setting parameters for channel 1 control point

random

10

AL1

000AH

Alarm setting value

--

By ALP1Parameters determine the alarm mode

For details, seeALP1Parameter Description

0

11

SC1

000BH

Error correction value

±20.0

Sensor errortranslationcorrection value

0

12

P1

000CH

Proportional band

0~200.0

adoptPIDWhen controlling,The proportional band determines the magnitude of the system's proportional gain, and the larger P,

The smaller the effect of proportion, the smaller the overshoot, but too small will increase the heating time.

(When P=0,The instrument willConvert to two position control,Some actuators that are not suitable for frequent start-up, such as fans, compressors, motors, etc., should use this method. Please refer to the parameters for detailsHY1The explanation section)

15.0

13

I1

000DH

integration time

0~3000

Set the integration time to release proportional control

The residual deviation that occurs will delay the time for the system to reach equilibrium if it is too large,Too small can cause fluctuations

240

14

D1

000EH

Differential time

0~200S

Set differential time to prevent output waves

Move to improve the stability of control

30

15

Hy1

000FH

Main control and alarm return difference

0.1~50.0

When the instrument is a two position control(Proportional tape)P=0)The dead zone between the opening or closing of the actuator to avoid frequent actions of the actuator.

When the main control is in heating mode:

whenmeasured valuePV1set valueSV1-HY1When the actuator opens, whenPV1SV1+HY1When, the actuator closes.

1.0

16

At1

0010H

Self-tuning parameters

0~1

0: Disable self-tuning 1: Enable self-tuning

0

17

CoL1

0011H

Heating and coolingmethodchoice

0~1

0: Heating function 1: Cooling function

0

18

ALP1

0012H

Alarm definition

0~4

0: No alarm; 1: Upper limit alarm

2: Lower limit alarm;3:Upper deviation alarm

4Deviation alarm 5Alarm outside the interval

6Alarm reported within the interval

1

Press separatelyCH2/CH3/CH4/CH5/CH6Press the key to enter2-6Channel menu,Set up using the same method

Press CH6Press the key for 3 seconds to enter 6Channel menu

sixChannel parameter setting

59

SP6

003BH

Ditto.

60

AL6

003CH

Ditto.

61

SC6

003DH

Ditto.

62

P6

003EH

Ditto.

63

I6

003FH

Ditto.

64

D6

0040H

Ditto.

65

Hy6

0041H

Ditto.

66

At6

0042H

Ditto.

67

CoL6

0043H

Ditto.

68

ALP6

0044H

Ditto.

Note: Please refer to the "Communication Protocol" section later for the measurement value addresses of each channel.

5、 Self tuning operation

First, set the settings and then enter the menuSet the hysteresis to around 0.5-1, set AT to ON, and the instrument enters a self-tuning state. The corresponding display window flashes and displays the "AT" character. At this time, the instrument is in positional control. After three oscillations, the instrument determines new parameters such as P, I, D and saves them, and resets to the control state.

sixError message

1.

When the instrument window displays "HH or LL", please check if the sensor wiring is correct.

2.