Welcome Customer !

Membership

Help

Beijing Jinyi Jiaye Technology Co., Ltd
Custom manufacturer

Main Products:

ybzhan>Products

Beijing Jinyi Jiaye Technology Co., Ltd

  • E-mail

    652819976@qq.com

  • Phone

    133-7175-8512

  • Address

    No. 18-D14697 Jianshe Road, Kaixuan Street, Liangxiang, Fangshan District, Beijing

Contact Now

Schneider apc SUVTR40KHS 40kva uninterruptible UPS power supply

NegotiableUpdate on 08/11
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Schneider APC's Smart UPVT

Product Details

Schneider APC's Smart UPS VT, rack mounted, 40kVA, 400V, with PDU and power on service

SUVTR40KHS

Characteristics of SUVTR0KHS

APC's Smart UPS VT, rack mounted, 40kVA, 400V, with PDU and power on service

  • On site replaceable power distribution panel
    Ensure compatibility of devices with different plug types
  • Locking room
    Prevent unauthorized access to UPS
  • Multiple cable entry points
    Provide flexibility for UPS placement in the computer room to facilitate cable installation to the terminal block
  • Resettable circuit breaker
    Can quickly recover from overload events.

Smart UPS VT features and advantages

Manageability
  • SmartSlot Slot Slot
    Customize UPS performance using management cards
  • Programmable frequency range
    Ensure compatibility with different input frequencies
  • LED status indicator light
    With the help of video indicators, device and power status can be quickly understood.
  • LSD monitor
    Alphanumeric display, displaying system parameters and alarms.
  • Audible Alarm
    Provide notification of changes to the conditions of the mains and UPS power supply
  • Compatible with Yingfei Manager
    In order to achieve centralized management through APC's Yingfei Manager software.
  • network management
    Realize remote power management for UPS through the network.
Serviceability
  • No need to replace the battery with tools
    Can quickly and conveniently replace batteries
  • Automatic self check
    Regularly self check the battery to ensure early detection of batteries that need to be replaced.
  • The module has been installed and can be shipped
    Capable of segmented transportation and testing of UPS before installation, as well as rapid installation
  • Modular design
    Through self diagnosis, on-site replaceable modules provide fast availability and reduce maintenance requirements
usability
  • Parallel battery module
    Provide higher availability through redundant batteries
  • Dual Power Input
    Connecting the UPS to two independent power sources increases reliability.
  • Scalable runtime
    Allow for quick increase of more running time when needed
  • Compatible with generators
    When using the generator power supply, ensure a clean and uninterrupted power supply to protect the equipment
  • Automatic internal bypass
    Provide common power to the connected load in the event of overload or malfunction of the UPS power supply.
Marketing Features
  • network management
    Realize remote power management for UPS through the network.
  • Manual maintenance of bypass
    No need to install external mechanical bypass, which can reduce installation costs.
  • Dual Power Input
    Connecting the UPS to two independent power sources increases reliability.
  • Scalable runtime
    Allow for quick increase of more running time when needed
  • Hot swappable battery
    Ensure a clean and uninterrupted power supply throughout the battery replacement process to protect the equipment
  • Input power factor correction
    By using a small generator and connecting wires, the installation cost is minimized
Sustainability
  • EU CoC for UPS
    Ensures that UPSs sold in the EU are highly efficient
system protection
  • Certified by security agencies
    The product has been tested and certified to ensure safe operation with the connected service provider equipment within the specified environment.
  • Frequency and voltage adjustment
    Poor frequency and voltage conditions can be corrected without using batteries, providing higher availability.
  • Cold start capability
    Provide temporary battery power supply when the mains power stops
Total Cost of Ownership
  • Temperature compensation battery charging
    Adjust the charging voltage according to the actual battery temperature to extend the battery life
  • Manual maintenance of bypass
    No need to install external mechanical bypass, which can reduce installation costs.
  • Input power factor correction
    By using a small generator and connecting wires, the installation cost is minimized
  • Intelligent battery management
    Obtain optimal battery performance, lifespan, and reliability through intelligent and precise charging technology.

output

  • Output power capacity

    32.0 K wattage/40.0 kVA

  • Maximum configurable power (watts)

    32.0 K wattage/40.0 kVA

  • rated output voltage

    400V 3PH

  • Output voltage annotation

    Can be configured for 3-phase rated output voltage of 380, 400, or 415 V

  • full-load efficiency

    96.0 %

  • Output voltage distortion

    Less than 5% at full load

  • Output frequency (synchronized with the main frequency)

    47-53 Hz (50 Hz nominal value)

  • Output frequency (asynchronous)

    50Hz +/- 0.1%, Rated 50Hz

  • Other output voltages

    380, 415

  • Peak load factor

    infinite

  • topology

    Dual conversion online

  • Waveform type

    sine wave

  • Overload operation

    60 seconds at 125% and 30 seconds at 150%

  • maximum output current

    64

  • Output Connection
    (12) IEC 320 C19 (Backup Battery)
  • bypass

    Built in maintenance bypass, built-in static bypass

input

  • Rated input voltage

    400V 3PH

  • input frequency

    40-70 Hz (automatic sensing)

  • Input terminal type

    Hard Wire 5-wire (3PH + N + G)

  • Working voltage range

    304 – 477 V

  • full-load efficiency

    96.0 %

  • Other input voltages

    380, 415

  • Maximum input current

    55.0 A

  • Input power factor under full load

    0.98

Battery and running time

  • Type

    VRLA

  • Typical charging time

    3 hours

  • Optional battery

    APC-Smart-UPS-VT-40kVA-400V-PDU-

Communication and Management

  • Interface ports (multiple)

    DB-9 RS-232 , SmartSlot

  • control panel

    Multi functional LCD display status management console.

  • Audible Alarm

    Sound and visual alarms: configurable delay

  • emergency shutdown

    yes

Physical parameters

  • tall

    1995 mm , 199.5 cm

  • wide

    600 mm , 60.0 cm

  • deep

    1075 mm , 107.5 cm

  • net weight

    289.0 kg

  • gross weight

    370.91 kg

  • Shipping height

    2095 mm , 209.5 cm

  • Shipping width

    756 mm , 75.6 cm

  • Shipping depth

    1206 mm , 120.6 cm

  • colour

    Black

environment

  • operation temperature

    0 - 40 °C

  • Relative humidity at work

    0 - 95 %

  • Operating height

    0-99.9 meters

  • storage temperature

    -50 - 40 °C

  • Store relative humidity

    0 - 95 %

  • Storage height

    0-15000 meters

  • Noise that can be heard 1 meter away from the surface of the device

    67.0 dBA

  • Online heat dissipation

    5459.0 BTU/hr

  • Protection level

    IP 20

Compliance

  • Management organization certification

    C-tick, CE, EN 50091-2, EN/IEC 62040-3, IEC 61000-3-2, IEC 61000-3-3, ISO 14001, ISO 9001, VFI-SS-111

  • Standard Warranty

    1-year repair or replacement service, start service



施耐德SPupsapc.jpgSchneider APC uninterruptible power supply, precision air conditioning, cabinet, PDU, KVM and other integrated computer room power distribution!

APC电源