Overview
The three-phase multifunctional calibrator is a high-precision instrument with three-phase AC/DC output. This instrument comprehensively applies advanced technologies such as three-phase synchronization technology, broadband power amplifier technology, and digital analog dual loop technology, and can output high-precision three-phase DC voltage, current, phase, harmonics, power, and electrical energy. It is suitable for verifying or calibrating various voltage meters, ammeters, power meters, power factor meters, phase meters, synchronization meters, electrical energy meters and other calibration devices, and can also be used as a standard source.
Product Details

1Three phase multifunctional calibratorPerformance Characteristics

This instrumentverifiableThe instruments are as follows:AC voltmeter, AC ammeter, AC power meter, reactive power meter, phase meter, power factor meter, frequency meter, synchronous meter, energy meter, DC voltmeter, DC ammeter, DC power meter, clamp meter, etc.

DC voltage output 1100 V, AC voltage output 770 V;

AC/DC current output 30A, AC output frequency 45Hz~65Hz.

Harmonic output 2-32 times, content ≤ 40%.

The AC output distortion is better than 0.2%, and the DC output ripple content is better than 0.2%.

Strong load capacity, ensuring stable and accurate measurement values under full load conditions, and can cover the calibration of analog meters.

The output has multiple value adjustment methods such as fixed-point output, rotary encoder, and step ratio.

Equipped with a large-sized LCD touch color screen, the measurement value display is intuitive and the operation is very convenient.

*Optional25T/50TThe coil can generate1250AEquivalent current for calibrating AC/DC clamp meters.

The output has comprehensive software and hardware protection functions, improving the long-term reliability of the device.

givenRS-232Interface. Through the upper computer software (optional), this device can be controlled by a computer for automatic or manual inspection, and the results can be processed and managed.

Equipped with a large capacity non-volatile memory, it can store the raw data of the tested instrument for reference and uploading.

The electric energy meter can be calibrated by detecting the load point or selecting the point according to the electric energy meter.

IIThree phase multifunctional calibratorTechnical Indicators:

AC voltage output

Range: 57.7V, 100V, 220V, 380V, 700V;

Adjustment range: (0~110)% RG;

Adjusting fineness: 0.01% RG, 0.1% RG, 1% RG, 10% RG;

Stability: 0.01% RG/1min;

Distortion: ≤ 0.2% (non capacitive load);

Output power: ≤ 30VA;

Basic error limit: ± 0.05% RG

AC current output

Range: 0.1A, 0.2A, 0.5A, 1A, 2A, 5A, 10A25A;

Adjustment range: (0~110)% RG;

Adjusting fineness: 0.01% RG, 0.1% RG, 1% RG, 10% RG;

Stability: 0.01% RG/1min;

Distortion: ≤ 0.2% (non capacitive load);

Output power: ≤ 100VA;

Basic error limit: ± 0.05% RG;

Flow power outputhand over

Basic error limit of active power: ± 0.05% RG

Basic error limit of reactive power: ± 0.1% RG

Active power stability: 0.01% RG/1min;

Reactive power stability: 0.02% RG/1min;

Phase output

Adjustment range: 0 °~359.999 °;

Resolution: 0.001 °;

Basic error limit: ± 0.05 °;

Power factor output

Adjustment range: -1.0~0~+1.0

Resolution: 0.0001;

Basic error limit: ± 0.0005;

Frequency output

Adjustment range: 45Hz~65Hz;

Resolution: 0.001Hz;

Basic error limit: ± 0.005 Hz;

Harmonic output

Harmonic frequency: 2-32 times;

Harmonic content: 0-40%;

Harmonic phase: 0 °~359.99 °;

DC voltage output

Range: 75mV, 300mV, 1V, 3V, 10V, 30V, 100V, 300V, 600V, 1000V;

Adjustment range: (0~110)% RG;

Adjusting fineness: 0.01% RG, 0.1% RG, 1% RG, 10% RG;

Stability: 0.01% RG/1min;

Output power: ≤ 30W;

Basic error limit: ± 0.02% RG;

Ripple content: ≤ 0.2%;

DC current output

量程: 30uA、100uA、300uA、1mA、3mA、10mA、30mA、100mA、300mA、2A、 10A、25A;

Adjustment range: (0~110)% RG;

Adjusting fineness: 0.01% RG, 0.1% RG, 1% RG, 10% RG;

Stability: 0.01% RG/1min;

Output power capacity: ≤ 60W;

Basic error limit: ± 0.05% RG;

Ripple content: ≤ 0.2%;

DC power output

Basic error limit: ± 0.05% RG;

Power stability: 0.01% RG/1min;

Measurement of electrical energy error40V400V

Basic error limit of active power: ± 0.05% RG;

Basic error limit of reactive power: ± 0.1% RG;

Tested electric energy pulse input

Pulse level: 5... 24V, ± 5mA;

Input frequency: ≤ 100kHz;

Standard power pulse output

Pulse level: 5V ± 5%, 100mA, with short circuit protection;

Output frequency: 50kHz

Other indicators

Weight: ≤ 25kg (excluding accessories and packaging boxes)

Volume: 520mm × 540mm × 205mm

Working power supply: AC220V ± 10%

Whole machine power consumption: ≤ 1KW

Working environment: temperature -20~40 ° C; relative humidity ≤ 85%.