Yokogawa EJA430E transmitter

NegotiableUpdate on 12/19
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
The EJA430E high-performance differential pressure transmitter adopts monocrystalline silicon resonant sensor technology, which is suitable for measuring the flow rate, liquid level, density, and pressure of liquids, gases, or vapors. The EJA110E converts measured differential pressure into a 4-20mADC current signal output, which can measure, display, or remotely monitor static pressure. It has functions such as fast response, remote setting, and self diagnosis.
Product Details

Henghe EJA430E pressure transmitter replaces Rosemount E+H Honeywell in Haidian District, Beijing

The EJA-E series products offer BRAIN, HART/HART (1-5VDC) low-power models, FF fieldbus, and PROFIBUS PA communication protocols, with standard configurations certified with SIL2 safety.

Henghe EJA430E pressure transmitter replaces Rosemount E+H Honeywell in Haidian District, Beijing

Range and Range:

Measurement range/range

MPa

psi(/D1)

Bar(/D2)

kgf/cm2(/D4)

H

range

5~500kPa

20 ~ 2000inH2O

0.05 ~ 5

0.05 ~ 5

scope

-100~500kPa

- -400 ~ 2000inH2O

-1~ 5

-1 ~ 5

A

range

0.03~ 3.5

4.3 ~ 500

0.3 ~ 35

0.3 ~ 35

scope

-0.1~3.5

-14.5~500

-1~35

-1~35

B

range

0.14 ~ 16

20 ~ 2300

1.4 ~ 160

1.4 ~ 160

scope

-0.1~16

-14.5~2300

-1~160

-1~160

Accuracy:

Measurement range

H

Reference accuracy

X ≤ range

±0.055%

X>Range

± (0.01+0.0063URL/range)%

X

70KPa(280inH2O)

URL (upper range limit)

500KPa(2000inH2O)

Measurement range

A

B

Reference accuracy

X ≤ range

±0.055%

X>Range

± (0.01+0.0045URL/range)%

X

0.35MPa(50psi)

1.6MPa(230psi)

URL (upper range limit)

3.5MPa(500psi)

16MPa(2300psi)

[When/HAC

Measurement range

H

Reference accuracy

X ≤ range

±0.04%

X>Range

± (0.005+0.0049URL/range)%

X

70KPa(280inH2O)

URL (upper range limit)

500KPa(2000inH2O)

Measurement range

A

B

Reference accuracy

X ≤ range

±0.04%

X>Range

± (0.005+0.0035URL/range)%

X

0.34MPa(50psi)

1.6MPa(230psi)

URL (upper range limit)

3.5MPa(500psi)

16MPa(2300psi)

Functional specifications:

output:

4~20mA HART/BRAN (output signal code D&J):

Two wire system with digital communication, 4-20mA DC output, can be set as linear or square root. BRAIN or HART FSK protocol loaded on 4-20mA signal, output range: 3.6mA~21.6mA.

1-5V HART (output signal code Q):

Three wire or four wire system 1-5V low-power type can be set with linear or square root HART protocol loaded on 1-5, output range 0.9~5.4VDC

Fault alarm (output signal code D&J):

4~20mA HART/BRAN (output signal code D&J)

Simulated output status during CPU failure and hardware error:

High output: 110%, ≥ 21.6mA DC (standard)

Low output: -5%, ≤ 3.2mA DC

1-5V HART (output signal code Q)

Simulated output status during CPU failure and hardware error:

High output: 110%, ≥ 5.4V DC (standard)

Low output: -5%, ≤ 0.8V DC

Explosion proof standard:

Chinese Explosion proof Standard: (NEPSI)

Factory Federation Certification: (FM)

European Community: (ATEX)

Canadian Standards Association (CSA)

IECEX: 本安 EXia EXic 隔爆IEC

Damping time constant:

The damping time constant of the amplifier can be adjusted within the range of 0.00~100.00 seconds through software, and the response time increases accordingly.

Refresh time:

Differential pressure: 45ms

Static pressure: 360ms

Zero adjustment:

Within the upper and lower limits of the membrane box range, the zero point can be adjusted arbitrarily.

External zeroing:

It can be continuously zeroed within the range, with a resolution of 0.01%. The range can be adjusted using the range setting switch on the meter head.

Built in display table (LCD display, optional):

5-digit display, 6-digit unit display, and bar chart.

The table can periodically display the following variables 1-4:

Measure differential pressure, percentage differential pressure, scale differential pressure, and measure static pressure.

Self diagnostic function:

CPU failure, hardware failure, configuration error, over limit reports for differential pressure, static pressure, and membrane box temperature. Users can configure differential pressure and static pressure high/low reporting.

Signal curve (output signal codes D, J&Q):

10 signal curves can be set to represent 4-20mA output, used for measuring boiler steam drum, cone tank liquid level, etc.

Normal operating conditions:

Ambient temperature

-40~85℃(-40~185℉)

-30~80 ℃ - (-22~176 ℉) with LCD display

Process temperature:

-40~120℃(-40~248℉)

ambient humidity:

0~RH

Work pressure (silicone oil):

H 500 kPa (2000 inH2O)

A 3.5 MPa (500 psi)

B 16 MPa (2300 psi)

Protection level:

IP66/IP67