Product features: It realizes low-temperature combustion of coal water slurry, solves the problems of easy coking, unstable operation, and poor safety caused by atomized suspension combustion of coal water slurry, and suppresses the generation and emission of thermal NOx
Product Features
L has achieved low-temperature combustion of coal water slurry, solving the problems of easy coking, unstable operation, and poor safety caused by atomized suspension combustion of coal water slurry, while suppressing the generation and emission of thermal NOx.
● Realized the cyclic combustion of coal water slurry particles after ignition and combustion, with high combustion efficiency.
The use of media materials composed of limestone and quartz sand, combined with low-temperature combustion technology, has achieved direct desulfurization during the combustion process of coal water slurry. The desulfurization system is simple and cost-effective.
The use of a separation and return combustion device has improved the utilization rate of limestone, reduced the amount of media material replenishment, and improved combustion efficiency.
Good load regulation characteristics, capable of stable operation within the range of 100%~30% rated load, and adaptable to the quality of coal water slurry.
Reduced the requirements for the quality of coal water slurry, resulting in lower pulp production costs.
Omitting expensive burners and easily malfunctioning atomizing slurry guns, the system does not require complex high-pressure slurry systems and filters, making it simpler and more reliable.
Stable operation, simple operation, high combustion efficiency, wide application range, suitable for boilers with various parameters.
lSHFS seriesCoal water slurry boilerMain performance parameters
|
Boiler model
|
SHFS6-1.25-J
|
|
project
|
|
Rated evaporation capacity (t/h)
|
6
|
|
Rated working pressure (MPa)
|
1.25
|
|
Rated steam temperature (℃)
|
saturation
|
|
combustion mode
|
室燃
|
|
Applicable fuel
|
Coal water slurry
|
|
Full load operation slurry consumption (Kg/h)
|
915
|
|
Heating surface area of the main body (㎡)
|
208
|
|
Heating area of economizer ㎡
|
72.4
|
|
Exhaust gas temperature (℃)
|
163
|
|
Thermal efficiency (%)
|
85.9
|
|
Maximum weight of transported item (t)
|
35.5
|
|
Maximum transport size (mm) (Length x Width x Height)
|
7100*3400*3540
|
Note: 1. The full load water coal slurry consumption of the boiler is calculated based on dw=17556KJ/Kg.
If there are any changes to the "product performance parameters" marked, the technical documents of the product at the factory shall prevail.