SF6 oxygen dual gas transmitter

NegotiableUpdate on 01/06
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
SF6 oxygen dual gas transmitter can be widely used in power safety monitoring systems: real-time monitoring of SF6 gas leakage and oxygen content in environments such as 35KV SF6 switch rooms, 500KV, 220KV, 110KV GIS rooms, and SF6 combination electrical equipment rooms in substations.
Product Details

SF6 oxygen dual gas transmitter

The detector includes a sulfur hexafluoride detection unit, an oxygen detection unit, a temperature detection unit, and a communication unit. The detection of sulfur hexafluoride uses ultrasonic detection technology to overcome the disadvantages of short service life and poor stability. It can monitor the changes in SF6 gas concentration and oxygen content in the environment in real time, and transmit the detected data to the SF6 monitoring host through RS-485 bus.

Modular design facilitates setting different monitoring factors as needed.

Choose high-precision electrochemical and long-life infrared sensors.

Suitable for simultaneous detection of multiple gases, Gonghu Si allows for flexible selection and use. Automatic compensation sensitivity for environmental temperature changes.

Structure considers aerodynamic principles to achieve automatic real-time sampling. Specially designed for SF6 gas leakage monitoring and alarm system in power equipment.

SF6氧气双气体变送器


SF6 oxygen dual gas transmitterTechnical Specifications

• Working voltage: AC/DC 220V ± 10%, 50Hz

• Power consumption:<10W at rated voltage

SF6 gas concentration measurement range: 0-3000ppm

SF6 concentration over limit alarm point: 1000ppm (national standard value)

• Oxygen content detection range: 0-25%

• Hypoxia alarm point: 18% (national standard value)

Remote communication method: RS485

name

address

Signal significance

Remarks

analog quantity(collection volume)The maximum number of registers that can be read and written each time is64a

D0

1000H

SF6gas concentration

SF6The gas content is represented by two bytes, such as1500ppmrepresented as05HDCH

SF6Upload value=measured value

D1

1001H

O2content

O2The content is represented by two bytes, such as25%represented as00HFAH

O2Content upload value=measured value*10

D2

1002H

temperature value

The temperature value is represented by two bytes, as25.0 ℃ is represented as 00H, FAH

Temperature upload value=measured value*10+500

D3

1003H

humidity value

The humidity value is represented by two bytes, such as32%represented as00H,20H

Humidity upload value=measured value

D4

1004H

Device number