The GIS partial discharge online monitoring system can monitor the partial discharge of high-voltage electrical equipment such as GIS in real time during operation, and provide timely warnings for insulation abnormalities and discharge faults of the equipment, achieving digitalization of substation maintenance.
Product Details

Product Introduction

GIS Partial Discharge Online Monitoring SystemIt can monitor the partial discharge of high-voltage electrical equipment such as GIS in real-time during operation, and provide timely warnings for insulation abnormalities and discharge faults of the equipment, achieving digitalization of substation maintenance.

Mainly used for GIS equipment of various voltage levels.

GIS Partial Discharge Online Monitoring SystemMain functions:

Avoiding the main electromagnetic interference frequency bands in the power grid, it has good resistance to electromagnetic interference and is insensitive to vibration and noise;

It is sensitive to various discharge defects, and even with external sensing detection methods, it can achieve sufficiently high detection sensitivity;

Based on the waveform characteristics of discharge pulses and the spectral characteristics of UHF signals, fault diagnosis and localization can be carried out;

Large effective detection range, few detection points, high detection efficiency, suitable for online monitoring.

work environment

Power supply: AC 85-260V, 50Hz/60Hz

Power consumption: 20W

Working environment temperature: -40 ℃~80 ℃ Humidity: 5%~95%, no condensation

Monitoring parameters:

Detection sensitivity: 5pC

Measurement range: 5pC~100nC

Ultra high frequency channel: 300MHz-1500MHz

Sampling accuracy: ≥ 12Bit

Sampling rate (synchronous): 50MHz per channel

Other parameters:

Measurement channels: 4 independent measurement channels, 1/2/3 are ultra-high frequency channels, and 4 are background noise channels

Monitoring synchronization: Simultaneously monitor all channels without any time difference

Interface: RJ45, RS485

Protocol compliance: UDP/IP protocol, standard RTU protocol

Channel power supply mode: no power supply