SF6 gas leakage monitoring and alarm systemMain functions
Real time monitoring and display:Real time triggering of detection signals, the host dynamically displays the SF6 concentration and oxygen content values of each gas transmitter. When the SF6 concentration exceeds 1000ppm or the oxygen content is below 18.0%, a red data color display will be prompted, otherwise the actual value will be displayed in normal color;
Automatic linkage control function:When the SF6 gas concentration exceeds 1000ppm or the oxygen content is below 18.0%, the system automatically controls the start of ventilation until the SF6 concentration and oxygen content return to normal;
Screen display:The host adopts a 7-inch touch color screen with screen saver function;
Timed ventilation function:The system can set 8 time periods for the fan to start and stop at regular intervals every day to ensure that indoor ventilation can be carried out as needed. The duration of fan start can be set;
Forced ventilation:When the fan is in a stopped state, press the main unit (start fan) button, and the system can perform forced ventilation; When the fan is in operation, pressing the host (stop fan) button will force the fan to shut down. The current fan operation status can be viewed in the bottom left corner of the screen;
Fire linkage function:The system has linkage with the fire protection system, and when it receives a fire alarm signal, it forcibly stops the fan from starting; Display the latest start and stop time of the fan; If the fan has experienced a start/stop action, the detailed record of the fan start/stop action and action type (such as manual start, timed start, alarm linkage) will be recorded in the system host event log. The staff can use this information to determine whether forced ventilation is needed before entering the switch room.
Human infrared sensing voice prompt alarm function:When the on-site host detects environmental abnormalities, it will sound a voice prompt alarm to remind staff to evacuate the scene and investigate the leakage situation. Under normal circumstances, when personnel approach the host area within 8-12 meters, the host will automatically provide voice prompts for the current environmental status; And it has voice on/off function;
Remote control and alarm functions:The on-site host provides four sets of alarm output nodes (one set of normally open passive dry contacts, one set of normally open pulse signals, one set of normally closed pulse signals, and one set of magnetic hold normally open signals), which act when SF6 concentration or oxygen content is abnormal, for users to use as needed;
Historical data query function:You can query the alarm history data of any time period by entering the historical data query interface in the menu item of the on-site host;
System self-test function:Design a separate self checking module on the internal hardware structure, which automatically resets and imports backup programs when abnormal or non normal operation of the main system program is detected, enabling the system to restore normal working status in a timely manner;
SF6 gas leakage monitoring and alarm system TH-SF100Technical Specifications
Working voltage: AC/DC 220V ± 10%, 50Hz;
Power consumption:<10W at rated voltage;
Accuracy level: 2.5 level;
SF6 gas concentration measurement range: 0-3000ppm;
SF6 concentration over limit alarm point: 1000ppm (national standard value), accuracy<5% FS;
Oxygen content detection range: 0-25%;
Hypoxia alarm point: 18% (national standard value), accuracy<1% FS;
Temperature detection range: -40 to+120 ℃ (accuracy ± 0.5 ℃);
Humidity detection range: 10-99% RH: accuracy ± 0.5% RH
Fan output power contact: 6A
Remote communication method: RS485;
On site host dimensions (mm): L330 × W250 × H65;
SF6 and oxygen detection unit size (mm): L162 × W150 × H38;
Size of temperature and humidity detection unit (mm): L162 × W150 × H38;
Monitoring historical data storage capacity: 5 million records;
Touch screen size: 7 inches;
Installation method of host and detection unit: wall mounted;
Working environment temperature: -25 ℃~70 ℃;
Working environment humidity: ≤ 95%;