TH-Z-SF10 online SF6 gas monitoring hostFunction Introduction:
In the environmentSF6Gas concentration detection function
●Oxygen concentration detection function in the environment
●Temperature and humidity detection function in the environment
●Real time display function of telemetry and remote signaling for all monitoring points in the environment
●Real time display of alarm information for all monitoring points in the environment
●Fixed value setting function
●SF6Gas concentration exceeding the standard and oxygen deficiency alarm function
●Oxygen deficiency or excessive SF6 concentration, forced exhaust function
●Automatic fan start function upon alarm
●Timed automatic exhaust function
●Manually force all fans to turn on or off,
●Historical data query, display, and storage functions
●Remote telemetry historical curve trend query and display function
●Enter the GIS room and automatically report the current environmental status function
●Multi monitoring point configuration function in different regions
●Multi point networking function, providing communication protocol and docking with substation backend database(reserve)
●Provide a universal communication interface and reserve the ability to interface with backend monitoring and fire protection systems(reserve)
●Alarm information storage and recording function
●Sound and light, voice alarm function
●Remote alarm function
●Human infrared detection and sensing function
●Data remote transmission function
TH-Z-SF10 online SF6 gas monitoring hostTechnical Specifications:
Working voltage: AC/DC 220V ± 10%, 50Hz
■Power consumption:<10W at rated voltage
■Accuracy level: 2.5
■SF6 gas concentration measurement range: 0~3000ppm
■SF6 concentration over limit alarm point: 1000ppm (national standard value), accuracy<2% FS
■Oxygen content detection range: 0-25%
■Hypoxia alarm point: 18% (national standard value), accuracy<1% FS
■Temperature detection range: -30~+99 ℃ (accuracy ± 0.5 ℃)
■Humidity detection range: 10~99% RH: Accuracy ± 3% RH
■Fan output power contact: 6A
■Remote communication method: RS485 Modbus RTU
■On site host dimensions (mm): L330 × W250 × H65
■SF6 and oxygen detection unit size (mm): L162 × W150 × H38
■Temperature and humidity detection unit size (mm): L162 × W150 × H38
■Monitoring historical data storage capacity: 5 million records;
■Touch screen size: 7 inches
■Installation method of host and detection unit: wall mounted
■Working environment temperature: -25 ℃~70 ℃
■Working environment humidity: ≤ 95%
■According to the provisions and methods of GB/T 17626, test the electromagnetic compatibility performance indicators of this device:
Electrostatic discharge, level 4
Radio frequency electromagnetic field radiation immunity, level 3
Electrical fast transient burst immunity, level 4
Surge (impact) immunity, level 4
Conducted disturbance immunity induced by radio frequency field, level 3
Power frequency magnetic field immunity, level 5
Pulse magnetic field immunity, level 5
Damping oscillation magnetic field immunity, level 5
Voltage sag and short-term interruption immunity, 60% UT, lasting for 10 cycles;
■According to the provisions and methods of GB/T 11287 and GB/T 14573, test the mechanical performance indicators of this device:
Vibration response, level 1
Vibration durability, level 1
Shock response, Level 1
Impact durability, Level 1
Collision, Level 1