HTRT-IITransformer capacity characteristic testerIt can measure the capacity of various distribution transformers and electrical transformers on site, without the need for additional power supply, making detection more convenient and faster
Combined with external power supply, voltage regulation, boost current and other equipment, it can measure characteristic data such as no-load current, no-load loss, impedance voltage, and load loss of various transformers
All test results have been automatically calibrated. You only need to input relevant parameters (such as temperature, no-load correction factor, etc.), and the instrument will automatically perform various corrections such as waveform distortion correction, temperature correction, non rated voltage correction, non rated current correction, etc., making the test results more accurate
In the measurement of transformer characteristics, the maximum voltage range can reach 750V, the maximum current range can reach 100A, and there is an internal protection circuit. When measuring, there is no need to switch gears to ensure measurement accuracy, and there is no need to worry about burning out the instrument due to incorrect gear selection
During transformer characteristic testing, the voltage and current ranges can be easily and flexibly expanded by simply connecting external voltage and current transformers, greatly expanding the testing range of the instrument
Large screen, high brightness LCD display, full Chinese menu and operation prompts, achieving a very friendly human-machine dialogue interface; Wide temperature and adjustable brightness LCD screen, adaptable to different environmental temperatures
Based on the no-load and load losses in the test results, the performance level of three-phase oil immersed distribution transformers and electrical transformers can be automatically estimated for on-site reference by the staff (currently, this instrument can only code the performance level of three-phase oil immersed transformer distribution transformers and electrical transformers. The inferred results are invalid for other types of transformers)
HTRT-IITransformer capacity characteristic testerTechnical Specifications
1. Built in power output range
Voltage: 0-10V
Current: 0-10A
2. Characteristic test power input range
Voltage: 0-750V
Current: 0-100A
3. Testing accuracy
Voltage and current: ± 0.2%
Power: ± 0.5% (Cos Φ>0.1), ± 1.0% (0.02<Cos Φ<0.1)
4. Working temperature
-20℃~+60℃
5. Charger power requirements
Commercial power AC160V~265V
6. Insulation degree
⑴. The insulation resistance between the capacity test, voltage, and current input points and the casing is ≥ 100M Ω
⑵ The charging power input can withstand a power frequency of 2KV (effective value) between the chassis, with a test duration of 1 minute
7. Volume
32cm×25cm×12cm