Welcome Customer !

Membership

Help

Wuxi Hangtai Electric Power Technology Co., Ltd
Custom manufacturer

Main Products:

ybzhan>Products

Water cooled DC high-voltage generator

NegotiableUpdate on 01/12
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
The ZGS-60kV/200mA water-cooled DC high-voltage generator is designed and manufactured specifically for leakage current and DC withstand voltage testing of water-cooled generators.
Product Details

ZGS-60kV/200mAWater cooled DC high-voltage generatorAdopting an intermediate frequency voltage doubling circuit. Apply new PWM pulse width modulation technology and high-power IGBT devices. And according to the theory of electromagnetic compatibility, special shielding, isolation, and grounding measures are adopted. makeWater cooled DC high-voltage generatorAchieved high quality

1. Due to the large conducted current in the windings of large water-cooled generators, it varies from 20-150mA under test voltage. If there is no DC high-voltage generator with sufficient capacity, it is impossible to boost the voltage;

2. At present, the output current of domestic DC high-voltage testers is generally within 10mA, and high-voltage generators with an output current of 200mA are blank;

3. For general high-voltage electrical equipment, DC testing can detect insulation penetration defects, while for motors, it can detect local insulation defects (insulation at the end of the stator coil), which cannot be replaced by other tests;

4. To accurately measure the leakage current of water-cooled generator sets, the 60kV/200mA seriesWater cooled DC high-voltage generatorSpecially designed compensation circuits for various interference currents can eliminate the influence of stray currents and polarization potential interference from the water collection pipe during testing, and truly measure the current of the test sample;


ZGS-60kV/200mAWater cooled DC high-voltage generatorTechnical Specifications

Specification (kV/mA) 60/200 60/300 80/200 80/300 90/200 90/300
Output voltage (kV) 60 60 80 80 90 90
Output current (mA) 200 300 200 300 200 300
Output power (W) 12000 18000 16000 24000 18000 27000
Voltage measurement error ≤ 1.0% ± 2 words
Current measurement error ≤ 1.0% ± 2 words
Overvoltage setting error ≤1.0%
ripple factor ≤3.0%
Voltage stability ≤1.0%
power supply voltage AC380V (three-phase four wire)
Chassis weight 25.0kg 25.0kg
Double pressure weight 65.0kg 70.0kg

For generators, conducting DC tests can sensitively and effectively detect stator winding end defects and gap defects. It has become a commonly used method in insulation testing of generator windings. Due to the large current conducted through the water collection pipe of large water-cooled generators, and depending on the water quality, the current generally ranges from 20 to 150mA under test voltage. Without a DC high-voltage generator with sufficient capacity, it will be impossible to increase the voltage. The ZGFS series leakage current tester for water-cooled generators is developed specifically for conducting leakage current and DC high voltage tests on generators, especially water-cooled generators. It is specially designed with compensation circuits for various interference currents, which can eliminate the influence of stray currents and polarization potential interference of the water collection pipe during testing, and accurately measure the leakage current of the water-cooled generator winding.

Similar Product Recommend